Ketidakseimbangan Beban Pada Gardu Distribusi PI0483 Penyulang Merapi di PLN ULP Indralaya

Authors

  • Daeny Septi Yansuri Universitas Palembang
  • Armin Sofijan Universitas Sriwijaya
  • Subianto Subianto Universitas Palembang
  • Siti Sailah Universitas Sriwijaya
  • Dwi Pratiwi Universitas Palembang
  • Anisah Harum Sari Universitas Palembang

DOI:

https://doi.org/10.32502/jse.v11i1.2474

Keywords:

Load Imbalance, Neutral Current, Distribution Transformer, Apparent Power, Feeder

Abstract

Load imbalance in a three-phase four-wire system can increase neutral current, conductor heating, and reduce utilization of distribution equipment. This study aims to: (1) determine the level of current imbalance and compare measured neutral current with the theoretical resultant; (2) calculate the apparent power associated with neutral current and its percentage relative to transformer capacity; and (3) determine load-balancing priorities based on electrical indicators. A quantitative descriptive case-study approach was applied using secondary data from the PI0483 Distribution Substation on the Merapi Feeder in Indralaya. The 100 kVA transformer supplies two circuits, with R-S-T phase currents of 26-15-16 A for Circuit I and 71-85-38 A for Circuit II. The results show imbalance levels of 24.56% and 27.49%, respectively. Measured neutral currents were 13 A and 47 A, while theoretical values were 10.54 A and 41.80 A. At an average phase-to-neutral voltage of 234 V, the apparent power associated with neutral current was 12.25 kVA based on calculated currents and 14.04 kVA based on measured currents, equivalent to 12.25%-14.04% of transformer capacity. Circuit II is prioritized for load balancing because of its higher imbalance, neutral current, phase-current range, and neutral-current apparent power. These findings highlight the importance of load redistribution and monitoring.

References

Aminullah, M. W., Putra, L., Gumilang, A. G., & Hurairah, M. (2026). Pengaruh Variasi Pembebanan Pada Kinerja Transformator 60 MVA di PT. PLN Gardu Induk Keramasan. Jurnal Surya Energy, 10(2), 92–98. https://doi.org/10.32502/jse.v10i2.1619

Badan Standardisasi Nasional (BSN). (2020). SNI 0225-2:2020 Persyaratan Umum Instalasi Listrik (PUIL) 2020 - Bagian 2: Desain instalasi listrik. Badan Standardisasi Nasional.

Chang, C.-K., Cheng, S.-T., & Boyanapalli, B.-K. (2022). Three-Phase Unbalance Improvement For Distribution Systems Based On The Particle Swarm Current Injection Algorithm. Energies, 15(9), 3460. https://doi.org/10.3390/en15093460

Guo, G., Zhan, X., Wang, J., Liu, Z., Feng, K., Peng, F., Gong, D., Tang, A., Xiang, C., & Wang, Z. (2024). Research On The Three-Phase Load Imbalance Control Of The Active Distribution Network Based On The Distributed Power Flow Controller. Frontiers in Energy Research, 12, 1414084. https://doi.org/10.3389/fenrg.2024.1414084

León-Martínez, V., Peñalvo-López, E., Montañana-Romeu, J., Andrada-Monrós, C., & Molina-Cañamero, L. (2023). Assessment Of Load Losses Caused By Harmonic Currents In Distribution Transformers Using The Transformer Loss Calculator Software. Environments, 10(10), 177. https://doi.org/10.3390/environments10100177

Nkinyam, C. M., Encho, L. T., & Mbaka, N. E. (2025). Design and Implementation of a 100 Kva Transformer Monitoring and Fault Detection System for Distribution Network. Journal of Electrical Systems and Information Technology. https://doi.org/10.1186/s43067-025-00213-0

Novfowan, A. D., Mieftah, M., & Kusuma, W. (2023). Alternatif Penanganan Losses Akibat Ketidakseimbangan Beban Pada Trafo Distribusi. ELPOSYS: Jurnal Sistem Kelistrikan, 10(1), 54–56. https://doi.org/10.33795/elposys.v10i1.716

Patilima, M. (2022). Pengaruh Ketidakseimbangan Beban Terhadap Losses Dan Pembebanan Transformator Distribusi. Jurnal Electrichsan, 11(1), 20–28. https://doi.org/10.37195/electrichsan.v11i01.85

Prayoga, A. B., & Suprianto, B. (2023). Analisis Pengaruh Ketidakseimbangan Beban Pada Transformator Distribusi Terhadap Rugi Daya (Losses) dengan DIgSILENT PowerFactory di PT PLN (Persero) ULP Ngunut. Jurnal Teknik Elektro, 12(2), 23–32. https://doi.org/10.26740/jte.v12n2.p23-32

Rizky, R. T. G., Zulfahri, Z., & Arlenny, A. (2022). Analisis Ketidakseimbangan Beban Jaringan Distribusi Tegangan Rendah Menggunakan ETAP. SainETIn, 6(2), 81–89. https://doi.org/10.31849/sainetin.v6i2.9648

Siregar, A. P., Tarigan, A. D., & Lubis, Z. (2024). Analisis Ketidakseimbangan Beban Akibat Penghantar Netral Jaringan Distribusi Sekunder. Power Elektronik: Jurnal Orang Elektro, 13(3), 298–301. https://doi.org/10.30591/polektro.v13i3.6967

Sutama, I. W., & Sari, I. A. L. N. (2023). Analisis Ketidakseimbangan Beban pada Gardu Distribusi KA 0251 Penyulang Gelogor Carik. Jurnal Ilmiah Telsinas, 6(2), 209–218. https://doi.org/10.38043/telsinas.v6i2.4893

Thango, B. A., & Bokoro, P. N. (2022). Stray Load Loss Valuation In Electrical Transformers: A review. Energies, 15(7), 2333. https://doi.org/10.3390/en15072333

Yasa, I. W. S., Wirajaya, A., & Adrama, I. N. (2024). Analisis Ketidakseimbangan Beban Pada Transformator Distribusi di PT PLN (Persero) ULP Bangli. Journal of Electrical and System Control Engineering, 8(1), 141–154. https://doi.org/10.31289/jesce.v8i1.11992

Downloads

Published

2026-09-16

How to Cite

Daeny Septi Yansuri, Armin Sofijan, Subianto Subianto, Siti Sailah, Dwi Pratiwi, & Anisah Harum Sari. (2026). Ketidakseimbangan Beban Pada Gardu Distribusi PI0483 Penyulang Merapi di PLN ULP Indralaya. Jurnal Surya Energy, 11(1), 64–71. https://doi.org/10.32502/jse.v11i1.2474

Issue

Section

Articles